| A. No, none of the parts of the 800E are interchangeable with the 800F. |
| A. Yes. It can switch DC motor or non-motor loads. See p. 2-116 in the A115 Catalog for switching capability. |
| A. Yes, within the 800F product line, all front of panel parts are compatible with both metal and plastic launches. |
| A. No. The electronic design of the E1 Plus overloads is for 50/60 Hz sinusoidal current applications. Recommend a bimetallic, eutectic alloy or E3 overload relays in VFD applications.
|
| A. No. The 193-M bimetallic overloads are recommended for these applications. |
| A. 100-C09 contactors do use the same power pole contact for the internal auxiliary contact as the main power poles and can be used as an additional power pole. The internal aux contacts on the 100-C12, 100-C16 and 100-C23 contactors can be used as a power pole but will have a 9 amp current rating for motor loads. |
| A. No. Single-phase specific catalog numbers are available with an electronic design specific for single-phase applications.
|
| A. The maximum number of auxiliary contacts, both normally open and normally closed, is eight (four side mounted and four front mounted). The maximum number of normally open contacts is four of which only two of these can be mounted on the side of the contactor. The maximum number of normally closed contacts is six, either side or front mounted. |
| A. The 800F non-illuminated operators can operate 6 circuits and the illuminated operators can operate up to 4 circuits. |
| A. The price is equivalent on an 800F LED module as on an 800F incandescent module. |